Experimental Research on Boiling Heat Transfer Performance of Alternative Medium HCFC123 Outside Tube

LIU Wen-yi,LI Wu,TAO Wen-Quan
DOI: https://doi.org/10.3969/j.issn.1007-2691.2005.04.010
2005-01-01
Abstract:Experimental studies on the pool boiling heat transfer of the new alternative medium, HCFC 123, outside smooth and fabricated tubes with holes are conducted at 5 ℃, 8 ℃ and 10 ℃. The variations of heat transfer coefficients with the heat flux and evaporation temperature are obtained. The experimental results show that the enhancement ratio of enhanced tube is 4.56-4.18. These results are compared with those of CFC11. The boiling heat transfer coefficient outside enhanced tube of HCFC123 is about 8% lower than that of CFC11.