Experimental Investigation on the Pool Boiling Heat Transfer Characteristics of R123 outside Single Horizontal Tubes

Li Wu,Tao Wenquan
DOI: https://doi.org/10.3969/j.issn.0253-4339.2005.04.007
2005-01-01
Abstract:Experimental studies on the pool boiling heat transfer of the alternative,R123,outside smooth and fabricated tubes with numbers of holes were conducted At the saturation temperature of 5℃,8℃ and 10℃,the experimental results agree with those from Cooper Equation with a maximum deviation of 10%.The variations of boiling heat transfer coefficients with both the heat flux and evaporation temperature were obtained.The experimental results show the enhancement ratios of fabricated tubes with numbers of holes is 4.56~4.18.The comparison with those of R11 were acquired.The boiling heat transfer coefficients outside the enhanced tube of R123 is lower than those of R11 about 8%.