Dynamic characteristic of the air-cooled refrigerator with two parallel-evaporators in the control of short-cycle switching

Zhenya ZHANG,Dong HUANG,Yongqiang LENG
DOI: https://doi.org/10.11918/j.issn.0367-6234.2017.01.022
2017-01-01
Abstract:For the two-circuit refrigerator with parallel evaporators,refrigerating cabinet and freezing cabinet could not get cooling capacity at the same time.This will lead to the increase in compressor-on time due to the fact that the compressor shuts down as the counterpart cut-out temperature in the freezing cabinet is reached.The dynamic characteristics of a parallel-evaporators refrigerator with short-cycle switching control were studied experimentally.Results showed that the refrigerant stored in the freezing-evaporator was immigrated gradually to refrigeratingevaporator due to pumping action of compressor after a startup.The capacity loss of the refrigerating evaporator due to the refrigerant migration decreased from 33.9% to 5.2%.In addition,the temperature of the freezer-sensor decreased from-16.5 ℃ to-17.8 ℃ in the first six short-cycles,but only decreased by about 0.3 ℃ in the next five short-cycles.The short-cycle switching control strategy can decrease the temperature in both refrigerating cabinet and freezing cabinet.However,the refrigerating-run time will be extended at the same time.These two factors should be comprehensive considered to make the compressor-on time shortest.