A two-combined-compressor refrigerator/freezer with cooling transformer

唐黎明,周苏明,陈光明,陈琪
DOI: https://doi.org/10.3785/j.issn.1008-973X.2013.11.015
2013-01-01
Abstract:To improve the energy saving performance of refrigerator/freezers (RFs), a new two-combined-compressor RF was put forward by adding a cooling transformer (CT) into conventional two-compressor two-circuit cycle RFs. The CT can transform part of refrigerator-cycle (R-cycle) low-grade cooling capacity into freezer-cycle (F-cycle) high-grade cooling capacity, then improve the RF's coefficient of performance (COP). Theoretical energy consumption was analyzed, influence factors such as the transformation ratio (TR) and compressor efficiency were taken into consideration in the process of simulated calculation. The result shows that: when the condensation temperature is 32°C, storage temperatures is -5°C and freezing temperature is -25°C, COP of two-combined-compressor RFs with cooling transformer can be improved 9.98% compared with COP of two-compressor two-circuit cycle RFs, while compared with COP of evaporator in series cycle RFs, the improvement rate is 13.38%.