Abstract:A program compiled by Visual Basic language was used to simulate a new combined absorption-compression refrigeration cycle for performance research,including the effect of generation temperature,evaporation temperature,condensation temperature,heat flux and refrigeration capacity on system performance which was compared with a conventional vapour compression refrigeration cycle.Simulation results show that when generation temperature increases,the coefficient of performance(COP) of new cycle increases first and then decreases.When evaporation temperature or heat flux increases,the COP of new cycle increases.When condensation temperature or refrigeration capacity increases,the COP of new cycle decreases.Under most simulation conditions,the COP of new cycle can be 10% higher than that of conventional vapour compression refrigeration cycle.The new cycle can not only reduce air conditioning load greatly,but also provide the possibility of efficient utilization of low grade energy such as solar energy.
What problem does this paper attempt to address?