Design of coaxial transformer for modular isolated DC/DC converters

Wei-jia TANG,Dao-zhuo JIANG,Rui YIN,Yi-qiao LIANG,Yu-fen WANG
DOI: https://doi.org/10.3785/j.issn.1008-973X.2017.08.022
2017-01-01
Abstract:An insulation method using high voltage insulated cable as the coaxial transformer winding was proposed aiming at the problem of high voltage insulation between transformer windings in DC/DC converters.The design and optimization method of the transformer was propased.A medium frequency coaxial transformer was designed in modular isolated DC/DC converter (MIDC) considering the actual pure DC wind farm.Transformer structure and parameter optimization was analyzed,and the optimization results were obtained.Ansys temperature field simulation of the transformer was conducted.A rated 250 kV · A medium frequency coaxial transformer was designed.Results showed that the optimal volume and weight were 0.022 3 m3 and 47.11 kg,the highest temperature of the transformer was 98.5 ℃ under fullload working condition,and the magnetic inductance and leakage inductance value both met the design requirements.Simulations verified the validity and feasibility of the proposed coaxial transformer design method.