Characteristics of single well systems in different initial aquifer temperatures

Wei SONG,Long NI,Yang YAO
DOI: https://doi.org/10.3969/j.issn.1006-7043.201212089
2014-01-01
Abstract:Because of insufficient research on single well groundwater heat pump systems , an experimental table for a physical simulation has been set up in order to study the flow and heat transfer law in these systems .Experimental research of initial aquifer temperature variations has been carried out .The results show that among the three single well systems, the standing column system's temperature variation between the inlet and outlet water is the maxi-mum, while its thermal influence scope is the minimum , and its load capacity is the lowest .When the initial aquifer temperature is 20℃in the heating mode , the heat transfer quantities of the pumping and recharging well system and the pumping and recharging well system filled with gravel are 2.0 and 2.2 times respectively with the standing col-umn well system .Moreover , the percentage of heat absorption change is greater than that of heat rejection change when the initial aquifer temperature changes to the same extent in the three single well systems .Therefore, initial aquifer temperature changes in heating mode should be paid attention in the heating dominated area .