Heat Transfer Characteristics of Standing Column Well

倪龙,姜益强,姚杨,马最良,李炳熙
DOI: https://doi.org/10.3969/j.issn.0493-2137.2009.11.016
2009-01-01
Abstract:The coupled heat transfer model for pumping pipe-well borehole-aquifer of standing column well(SCW)was established based on the conservation of energy. The correctness of the model was validated via the numerical simulation presented to an in-situ test of SCW. Investigation on heat transfer characteristics was presented to a typical SCW. The results show that dramatic changes occur in pumping groundwater temperature and the changes amount to 7.℃ during heating period,which reduce the ability of the system to deal with the unexpected load and increase the power consumption of heat pump. The original groundwater exchange between the borehole and aquifer bore nearly 23.4% loads,and almost do not change with time. The heat-affected zone of aquifer is small(approximate 14 m).Therefore,the well spacing for SCWs can be as small as 15.m.