Three-dimensional Numerical Study on Evaporation Water Losses in a Natural Draft Wet Cooling Tower

Ru-yun GAO,Nianzeng YUN,Yu-wei LI,Yang CAO,Bo-shu HE
DOI: https://doi.org/10.3969/j.issn.1674-8492.2015.04.014
2015-01-01
Abstract:Taking a natural draft counter-flow wet cooling tower as the research object, a three-dimensional numerical simulation model was established using commercially available software, fluently, with consideration of the influence of resistances from the fill, the water collector and the heat and mass transfer of the fill. Through the operation data and the empirical formula, the established model was verified. The results show that the established 3-D numerical calculation model is suitable for cooling tower flow and heat and mass transfer calculations. The influence factors of flow field characteristics and evaporation water losses was calcu?lated and analyzed, especially the influence on the evaporation water losses and the heat exchange. The re?sults also show that the cooling effect enhances and the outlet temperature drops when the equivalent diame?ter of raindrops reduces. With the increase of circulating water or the rise of inlet water temperature, the evaporation loss increases. Therefore, reducing the tower circulating water heat is an effective way to reduce the evaporation losses.
What problem does this paper attempt to address?