Influence Mechanism of the Three-Zone Synergistic Efficiency-Enhancing Pattern on the 3D Flow Field and Thermal Resistance Characteristics for Wet Cooling Towers
Jichong Yang,Xiaojing Yuan,Mingyong Wang,Suoying He,Ming Gao
DOI: https://doi.org/10.1016/j.icheatmasstransfer.2023.107170
IF: 6.782
2023-01-01
International Communications in Heat and Mass Transfer
Abstract:For a super-large natural draft wet cooling tower (S-NDWCT) equipped in a 1000 MW unit, a 3D numerical model of the three-zone synergistic efficiency-enhancing pattern (TSEP) was established and validated. This study focused on the influence mechanism of the three-zone parameters on the 3D flow field and thermal resistance characteristics, including the installation height h, installation angle theta, total coverage area S, length L and number n of the split-flow plate, water distribution partition radius R1, the proportion of inner zone water amount P, and fillings partition radius R2. The results showed that the TSEP reconfigures and comprehensively optimizes the airflow field, and presents the more uniform air-water ratio and water temperature fields. The volumetric heat transfer coefficient hv increases and then reduces as h, theta, S, n, R1, P and R2 increase, and increases continuously with increasing L in the range studied. Additionally, the ventilation G increases and then reduces with the increase of h, theta, R1 and P, increases with rising S, n and R2, and reduces with L increases. Finally, the relatively optimized values of the three-zone parameters are obtained. In this case, compared with a conventional tower, the hv and G increase by 11.3% and 10.6%, respectively.