Measurement and Appraisal of the Corrosion of the Pipe Network of Urban Nature Gas

RUAN Jing-hong,HOU Shi-ying,LU Min-xu,Zhang Guo-an,DUAN Wei,LI Xia-xi
DOI: https://doi.org/10.3969/j.issn.1004-9614.2005.03.007
2005-01-01
Abstract:Take the Er Gao ya line in Beijing as an example. The measuring and appraisal methods for the security of the urban pipe network were introduced. The results of measurement and appraisal of the soil environment, the protective coating and the pipeline corrosion indicate that the water content of soil is high, presenting a slight alkalinity. The corrosiveness of soil is rated medium. The relatively thin anti-corrosion coating of the pipeline is ageing seriously, and has some damaged parts with a poor protective performance. Part of pipeline has destroyed already. Pipes at the No. 003 trail hole do not meet the intensity safety demand. The surplus wall thickness of other trail holes can offer still enough intensity under present service states, but the pipeline has been corroded, so it is proposed to adopt strengthening measures for a check-up or for athodic protection.
What problem does this paper attempt to address?