RESEARCH ON FEASIBILITY OF ON SITE DC INSULATOR DETECTION BY ELECTRIC FIELD METHOD

SHEN Xiao-jun,JIANG Xiu-chen,CHENG Yang-chun,ZENG Yi,QIU Dong-feng
DOI: https://doi.org/10.3321/j.issn:1000-3673.2005.04.009
2005-01-01
Abstract:Except DC voltage, there are a lot of high-order harmonic components in DC transmission voltage. By means of analyzing the constituents of electric field of DC insulators being operated, the distribution characteristics of DC and harmonic electric fields of DC insulators are researched. The feasibility of on-line detection of DC insulators by use of DC electric field method and harmonic electric field method is discussed. The harmonic (DC) electric field methods are the very methods that detect the DC insulators in on-line mode by use of the harmonic (DC) component electric fields of DC insulator string being operated. Theoretical analysis and test results show that the distribution of harmonic electric filed is more stable, by which the inner insulation failures of composite insulators and zero-value porcelain insulators can be effectively detected, so harmonic electric field method is a feasible on-line method to detect DC insulators.2004-11-25。
What problem does this paper attempt to address?