Resonance suppression for grid-connected multi-inverter based on active damping method

Guo-feng HE,De-hong XU
DOI: https://doi.org/10.15938/j.emc.2017.10.009
2017-01-01
Abstract:Under the influence of grid impedance, the resonance will occur among the grid PV inverters which are connected to grid with LCL filters. In order to restrict the resonant of Multi-inverter parallel un-der grid-connected mode,an active damping control strategy,based on closed-loop control model for mul-tiple grid-connected inverters,is proposed. The equivalent mathematical model of the closed-loop control circuit was established by the Thevenin Equivalent Principle firstly. Then the resonant mechanism based on the established control mathematical model was analyzed. To effectively suppress the resonant of Multi-inverter parallel,the active damping control method by the feedback of capacitor current of LCL filter was adopted,and the mathematical model of multiple inverters with the active damping control was given. The influence of active damping coefficient on the steady and dynamic response of the grid inverters was studied according to the resonance equation. Finally,the presented control method was verified by exper-iments on three grid inverters by comparing with and without damping control algorithms. The experimen-tal results show that the presented control strategy can effectively suppress the resonance among paralleled inverters.
What problem does this paper attempt to address?