Abstract:Gasoline pool fires with special fire power was used to ignite expandable polystyrene(EPS)foam sand-wichpanels treated with asbestos cloth and fireproof strip.The ISO9705 full-scale room/corner test apparatus and thermocouple trees were adopted to measure the reaction-to-fire properties and fire spread properties.Results show that thepeak heat release rate values of the EPS panels treated with asbestos cloth and fireproof strip decreasedby 34.3%, and 9.6%,,30.2%, and 8.2%,respectively,compared with those treated with sealing,while the total heat release values decreased by 12.5%, and 14.1%,respectively.Therefore,fire partitions have highheat insulation to prevent heat spread and the reaction-to-fire property(pyrolysis,melting,combustion etc.)of EPS.In general,the fire partition ability of asbestos cloth is much stronger than that of fireproof strip.