Simulation and experiment on performance of air cooler with variable fin pitch in frosting conditions

Hai-jie QIN,Wei-zhong LI,Wei-ying ZHU
DOI: https://doi.org/10.13738/j.issn.1671-8097.2014.03.003
2014-01-01
Journal of Thermal Science and Technology
Abstract:A two-dimensional transient model for frost formation phenomenon on an air cooler with variable fin pitch has been developed to calculate and optimize the performance of the air cooler under frosting conditions.The proposed model is based on the molecular diffusion model.In the model,the mean frost thickness at the windward side of the control volume of the evaporator is taken as a variable for iterative calculations of the air volumetric flow rate to improve numerical accuracy. The numerically and experimentally obtained performance of the air cooler with variable fin pitch and constant fin pitch was compared.The results show a good agreement between the calculated values and the experimental data of the volumetric flow rate and the heat transfer rate of the air cooler with the relative difference less than 5%.Compared to air coolers with constant fin pitch under the same operating condition,the decrease in the volumetric flow rate of the air cooler with variable fin pitch is smaller.Therefore,it corresponds to a longer defrost cycle and larger heat transfer rate.
What problem does this paper attempt to address?