Energy conservation performance of finned-tube heat exchanger under frosting condition

Wang Hou-hua
Abstract:In order to investigate the refrigeration performance of finned-tube heat exchanger with changing fin spacing and symmetrical holes under frosting conditions,a wind-tunnel experiment on the energy conservation performance was carried out.The experimental results show that in the range of head-on-average velocity from 1.87.4.30 m/s,comparing the finned-tube refrigeration heat exchanger with no-changing fin spacing and holes,in the same experimental condition and geometric size,the cooling capacity of the former exchanger increases by 7.6%;the surface of the fin heat transfer coefficient raises by 18.26%;and the resistance decreases by 48.85% with saving 21.43% metal material of fin in lower velocity.
Materials Science,Engineering,Environmental Science
What problem does this paper attempt to address?