Determination of H2S in SF6 Decomposition Products by Ultraviolet Absorption Spectrometry

YANG Yuling,GUO Xinliang,CUI Zhaolun,XIA Huanhuan,YANG Xueying,ZHANG Xiaoxing
DOI: https://doi.org/10.13336/j.1003-6520.hve.20180425001
2018-01-01
Abstract:Determination of H2S in SF6 decomposition products plays an important role in assessment of the insulation state in SF6 insulated electrical equipment. H2S can be detected by ultraviolet absorption spectrometry for its absorption in the band of 190~230 nm. We set up an ultraviolet detection platform for the determination of H2S. However, the sensitivity of H2S detection was low because the absorption spectra were easy to be interfered by spectral scatting and high-frequency noise. Therefore, ultraviolet difference algorithm and wavelet function were used for volume fraction inversion to obtain the relationship between spectral data and gas volume fraction. The research results show that there is a good linear relationship between the frequency domain information obtained by spectral data extraction and the concentration, the method shows good linearity (R2=0.999 9) and the volume fraction limit of the detection is 0.590×10-6. The obtained inversion expression was used for the actual data detection, and a good detection effect was obtained. The method is of good detection repeatability and high sensitivity, and it can be integrated into portable testing equipment, which is suitable for on-line detection of trace H2S in SF6 insulated electrical equipment.
What problem does this paper attempt to address?