Calculation Method for Technical Parameters of On-load Tap Changer in Phase Shifting Transformer

Xin LIU,Guishu LIANG,Litong WANG,Fei GAO,Bo LI,Jinzhong LI
DOI: https://doi.org/10.13336/j.1003-6520.hve.20170303020
2017-01-01
Abstract:The breaking step voltage and current of on-load tap changer in two-core phase shifting are closely related to on-load conditions.To determine the effects of on-load conditions on technical parameters of the on-load tap changer,by introducing the working principle and operational characteristics of two-core phase-shifting transformer,we deduced a practical and accurate formula about step voltage under the conditions of on-load.Taking a 230 kW150 MVA two-core phase-shifting transformer as an example,we verified the accuracy of the proposed formula by comparing the MATLAB/SIMULINK simulation results with the results obtained by the formula.Then,we analyzed the relationship between the step-voltage and the load characteristics.It is demonstrated that more accurate technical parameters of the on-load tap changer can be determined by the calculation method based on the on-load conditions.Furthermore,a conclusion is drawn that the step-voltage increases with the growth of power factor by analyzing the influence of the load power factor on the maximum step-voltage.