A Method of Adjusting Tap of Converter Transformer for Load Flow Calculation of AC/DC Power System

LIU Chong-ru,ZHANG Bo-ming,SUN Hong-bin
DOI: https://doi.org/10.3321/j.issn:1000-3673.2006.09.004
2006-01-01
Abstract:The action of converter transformer in HVDC transmission system is analyzed. In load flow calculation of AC/DC power system the adjustment of converter transformer’s tap changer is taken into account, the mathematical model and method to adjust the position of taps are proposed and their simulation results for two-terminal and three-terminal HVDC transmission systems are given. Simulation results show that the proposed method can effectively detect the out-of-limit of operation angle and operation voltage and reduce the reactive power absorbed by converters as possible according to different adjusting requirements.
What problem does this paper attempt to address?