Mechanism and peak value calculation of AC tie-line power swing caused by DC blocking

Jingzhe Tu,Li Yang,Yong Huang,Hongsheng Zhao
DOI: https://doi.org/10.3969/j.issn.1006-6047.2013.01.003
2013-01-01
Abstract:The AC tie-line power swing caused by DC blocking is actually a step disturbance problem, which, because the DC blocking excites the oscillation mode between two interconnected power grids, should be studied with the second-order system step response theory. Since the step disturbance power excited by the interior DC blockings is different from that by the exterior DC blocking, the mechanism of AC tie-line power swings excited by different DC blockings are studied separately. The approximate calculation of AC tie-line power swing peak is given and its influential factors are summarized. The AC tie-line power swing peak is calculated respectively by the proposed approximate calculation and the power system simulation software for a real UHV interconnected power grid, which verifies the feasibility and correctness of the proposed calculation method.
What problem does this paper attempt to address?