Effect of Rabbet Assembly Position of Moving and Static Contacts on Performance of Vacuum Interrupter

Min LI,Da LI,Xiaoqin WANG
DOI: https://doi.org/10.13296/j.1001-1609.hva.2017.03.017
2017-01-01
Abstract:To understand the effect of rabbet assembly position of moving and static contacts on performance of vacuum interrupter,simulation and experimental methods were employed to analyze the performance of a vacuum interrupter with different rabbet assembly position,and the effects of rabbet assembly position on magnetic flux density and arc pattern were obtained.The results showed that when the dislocation degree of rabbet was 45°,the maximum value of magnetic flux density was 63.71,64.31 and 64.18 mT,respectively;the arc had smaller size,more stable movement,and the voltage of 36 V;and the interruption performance of the vacuum interrupter was better.So it is concluded that the interruption performance of the vacuum interrupter can be improved at 45° dislocation of rabbet in assembly.