Influence Factors of Initial Internal Corrosion of Grey Cast Iron Pipes in Water Distribution System

Yu-long YANG,Han-qing TANG,Li-qin GU,Hao-fang WANG,Tu-qiao ZHANG,Cong LI
DOI: https://doi.org/10.19853/j.zgjsps.1000-4602.2018.15.010
2018-01-01
Abstract:Refer to the values specified in the Standards for Drinking Water Quality (GB 5749 - 2006), the influence of pH, DO, residual chlorine, temperature and NaCl concentration on the initial internal corrosion of the grey cast iron pipes were studied. The analyses on the corrosion mass, the corrosion rates and the sensitivity of the influence factors were carried out. The results showed that the corrosion mass and the corrosion rate increased with the increase of DO, residual chlorine, NaCl and temperature. A higher corrosion rate was observed in the acidic environment. During the corrosion process, pH demonstrated a pattern that firstly increased, then decreased, and finally remained constant. The decay of the corrosion rate was positively correlated to the decay of the residual chlorine and DO. The grey correlation analysis method was utilized to analyze the significance of various factors on the corrosion process, which in descending orders were DO > temperature > pH > NaCl > residual chlorine. The effect of dissolved oxygen on corrosion was greatest, followed by the temperature, and the influence of residual chlorine was the least.
What problem does this paper attempt to address?