Abstract:To resolve the serious breakage and leakage problems for the grey cast iron water mains buried in the early years in the water-supply system, pipe stresses were firstly calculated based on the pipe soil inter-action model, and the corrosion depth was predicted by the corrosion model. Then, the residual strength associated with corrosion was evaluated, and a failure prediction model was given by using the failure crite-rion for the cast iron. Monte Carlo (MC) simulations were used to perform the probabilistic analysis. The given model fully considers the influences of corrosion, external loads and uncertainties on the pipe failure. Results show that the pipes will not be failed when only considering the external loads. The corrosion is one of the very important factors contributing to the pipe failure. The probability density distribution of the safety factor of the pipe appears a lognormal distribution. The hazard of the pipe failure is large in 20-50 years, and it becomes small after 80 years and decreases with the time. The influence on the failure probability is large for considering soil bedding lost induced by the breakage or uneven settlement when the corrosion depth reaches a certain depth.