Effects of Flow Path Layout on the Performance of Microchannel Parallel Flow External Heat Exchanger

Qingfeng Xue,Xiaoqing Zhang,Huiming Zou,Changqing Tian
DOI: https://doi.org/10.19620/j.cnki.1000-3703.20161278
2018-01-01
Abstract:An external heat exchanger simulation model was built based on Dymola software, and a heat pump system test bench was set up to study the influence of flow path layout on the performance of micro-channel parallel flow external heat exchanger and pressure drop. The investigation results show that, under heating conditions, heat transfer has the best heat exchange and pressure drop with flow path layout of 1:3, and their errors between test and simulation results are within 6% and 14% respectively; whereas under cooling conditions, its heat exchange amount is greater than the other two layouts, whereas it has greater pressure drop, with flow path layout of 1:3, and their errors between experimental and simulation results are within 14% and 11% respectively. Considering the heat exchange amount and pressure drop performance of the external heat exchanger in heating and cooling conditions as a whole, the flow path layout of 1:3 is the optimal one.
What problem does this paper attempt to address?