Optimal Control of Gas Temperature Deviation in a 660 MW Supercritical Tangentially-fired Boiler

Anlong GUO,Qingyan FANG,Sinan ZHAO,Ying WU,Yongjun XIA,Cheng ZHANG,Gang CHEN
DOI: https://doi.org/10.3969/j.issn.1674-7607.2017.05.001
2017-01-01
Abstract:Aiming at the phenomenon of large gas temperature deviation between the left and right side at furnace outlet of a 660 MW supercritical tangentially-fired boiler,numerical simulation was conducted,and subsequently the results were compared with that of experiment.Results show that the simulation data agree well with experimental values,and the gas temperature deviation is found to be caused by residual rotating air flow,which can be reduced by counterclockwise adjusting the SOFA horizontal swing angle,reducing the opening of secondary air damper and increasing the opening of SOFA damper,etc.After taking above measures,the economy and safety of the boiler are improved.