Anti-interference analysis of chiller model based on characteristic parameters

ZHAO Lin,LIANG Caihua,ZHANG Xiaosong
DOI: https://doi.org/10.11817/j.issn.1672-7207.2018.05.030
2018-01-01
Abstract:A modeling method which lumps unknown structural parameters of chiller and gets the lumped parameters by measured data was used to build the chiller model. The influence of measurement error in measured data on the modeling method and accuracy of the model was studied. The results show that when the measured data of freezing/cooling water flow, the inlet/outlet temperature and other units have the maximum measurement error within the accuracy range of the measuring instrument, the relative error of simulated coefficient of performance (COP) is less than 2.5%, which indicates that the chiller model based on characteristic parameters has high anti-interference ability.