Partial Discharge Aging of Epoxy Insulation at Different High-Frequency Pulse Parameters and Environmental Stresses
Xingyu Shang,Lei Pang,Qinhao Bu,Qiaogen Zhang
DOI: https://doi.org/10.1109/tdei.2024.3502581
IF: 2.509
2024-01-01
IEEE Transactions on Dielectrics and Electrical Insulation
Abstract:The voltage stress on high-frequency transformers (HFTs) features higher levels of repetition frequency, operating voltage, voltage d V /d t and grid voltage superposition, which challenges the epoxy insulation of HFTs exposed to partial discharges (PDs). Wide ranges of voltage parameters (frequency, voltage, rising edge and DC bias) and environmental stresses (temperature, humidity, gas, pressure) are applied to the sphere-gap-insulation-plate structure for PD aging analysis. New patterns are found in this study. For example, the shape of the rising edge affects the lifetime, and the influences of humidity and DC bias are non-monotonic. Surface charge decay and voltage d V /d t have key impacts on the discharge pattern. Early failures with pulse frequencies of 50 kHz and 100 kHz are attributed to the interaction of humidity and electric field. The erosion rate is lower at oxygen-free ambient, while higher with CO 2 gas. PD parameters (PD number, PD amplitude, PD delay, PD ignition voltage and PD frequency) and phase-resolved PD (PRPD) patterns are measured with ultra-high frequency (UHF) method and discussed for all aging conditions. Cumulative PD amplitude and cumulative PD energy have good correlation to experimental lifetime values. However, due to the transition of PD regime, the fit model has less explainability on the influence of voltage, humidity, gas and pressure on the lifetime, which is rarely revealed before.