Online Monitoring System of HVDC Breaker based on PAC Data Acquisition Technique

Jun Wang,Zhihua Li,Tao Ning,Wei Chen
2011-01-01
Abstract:In order to get the real-time operating state of the oscillation circuit of HVDC breaker, and calculate the RLC parameters of the oscillation circuit, there put forward a online monitoring system of HVDC breaker's oscillation circuit based on PAC (Programmable Automation Controller) Data Acquisition Technique. The hard ware and software were designed to achieve this goal. In this system, a Hall sensor was used to linearly transform the oscillation current into voltage signal, then the voltage was gathered by PAC Data Acquisition system, after stored on local disk of PAC, the data was transmitted to the data processing center. After these, the RLC parameters of the oscillation circuit could be calculated automatically. With this online monitoring system of DC breaker's oscillation circuit, we have done experiments in our lab and in Gezhou Dam convertor station. The experimental data proved that this system do not have any impact on the electric power system, the most important is that it can accurately gather the oscillation current :signal at high definition, and calculate the RLC parameters quickly and exactly. We can master the state of the breaker whether it can interrupt the current normally with these parameters.
What problem does this paper attempt to address?