On line monitoring of operation time for SF_6 high-voltage circuit breakers based on wavelet algorithm

WU Zhen-sheng,WANG Wei,YANG Xue-chang,LANG Wei-guo
2006-01-01
Abstract:With the development of the technologies to monitor the High-Voltage Circuit Breaker(HVCB),more contents of the maintenance can be operated on-line.Based on researching the operation principle of the HVCB,a new method was developed in this paper to calculate the operation time of the SF6 HVCB switching on line,which analyzed the forces applied to the contactor of HVCB in detail to estimate its moving conditions.With the results of the forces analysis,using wavelets analysis to get rid of the noises and disturbs of the contact travel signal,further processing of the signals can give the time of the switching on and off.The wavelets analysis can remove the noises and disturbs without distorting the signals,it helps to get the accurate time of the switching moment.The operation data from the lab shows that the algorithm is accurate and simple.