Analysis on non characteristic harmonic circulating current in parallel inverter system and its suppression measures

Yinghong Hu,Chun Deng,Jinsong Wang,Yu Li,Xiaorong Xie,Shaoyu Liu,Jia Diao,Jiajia Ren
DOI: https://doi.org/10.13335/j.1000-3673.pst.2016.07.035
2016-01-01
Abstract:In Jibei power grid, non-characteristic harmonic circulating current appeared several times and a fault occurred in parallel converters in a 500 kV station. Taking this fault as an example, recorded fault data were analyzed, finding out non-characteristic harmonic circulating current existing in several parallel converters. Analysis of relationship between the problem and parallel converter topology indicated that the problem was liable to appear in cascaded H-bridge multilevel converters. Reappearance of the phenomenon was realized with electromagnetic transient simulation. Simulation results showed validity of the proposed conclusion. Finally, countermeasures were proposed to solve the problem.