Performance Analysis and Improvement of Single-Terminal Fault Location in Transmission Lines with DFIG Wind Farm Connecting

Bin WANG,Yuan-yuan LU,Bing YUAN,Yan LI
DOI: https://doi.org/10.3969/j.issn.1673-9140.2015.03.001
2015-01-01
Abstract:The variation characteristics of sequence equivalent impedance of MW DFIG wind farms are absolutely different due to the complicate impacts of wind generator unit type,capacity,and low voltage ride through control strategy etc.The dynamic changing of the sequence equivalent impedance of wind farm will also indirectly influence the measurement at the power system side by the effects of fault branches,hence there are big fault location errors for single terminal im-pedance fault location at power system side,and for two terminal impedance fault location.Ac-cording to the problem,this paper built a MW DFIG wind farm model and analyzed its transient output characteristics,quantified the key factors producing the fault location errors,and then proposed an improved algorithm based on phase error compensation.The simulations proved good performance of the novel algorithm.The achievement in this paper also can apply into the design and setting of distance protection in transmission lines with wind farms connection.