High impedance fault analysis and location of single-phase-to-ground fault in feeder with multiple DGS connections

Xuan Ren,Bin Wang,Xinzhou Dong
DOI: https://doi.org/10.1049/cp.2019.0330
2019-01-01
Abstract:Since the single-terminal fault location in the collection line of wind farm is seriously affected by the complex wind turbine branch, the traditional fault location methods are not applicable to the wind farm anymore. According to the traditional single-terminal impedance fault location method, the zero-fault sequence network of wind farm is studied. Generally, the box transformer is delta-connected to the wind turbine, so when a single-phase-to-ground fault occurs, there is no zero-sequence fault current flowing in the wind turbine branch. Then an improved fault location algorithm for the collection line of wind farm is proposed. In this method, with the wind turbine branch current considered, the collection line of wind farm is divided into several sections, and the fault location is searched step by step after the fault. This method can effectively reduce the influence of wind turbine branch on fault location and the fault distance and the fault resistance can be calculated accurately. Based on PSCAD simulation, the proposed fault location algorithm is validated.