Field Test and Calculation Methods of Infiltration Rate in Large Space Buildings such as Airport Terminals

Lin LIN,Xiaochen LIU,Tao ZHANG,Xiaohua LIU,Qingpeng WEI
DOI: https://doi.org/10.13614/j.cnki.11-1962/tu.2018.04.02
2018-01-01
Abstract:Unorganized air infiltration is an important factor influencing the temperature and humidity in large space buildings such as airport terminal.This paper mainly studies the calculation methods of air infiltration in large space buildings through comparison.The wind speed test method,tracer gas method,moisture content method and heat balance method for investigating air infiltration are introduced.Error sources and influencing factors of different methods are then quantitatively analyzed.The results show that wind speed v,and indoor and outdoor CO2 concentration difference △C,moisture content difference △d,and temperature difference △t are important factors that affect the accuracies of different methods respectively.Based on the four methods,field test and calculation of infiltration rate in the transitional season is carried out in an airport terminal,in the hope to provide an effective tool for analyzing the influence of air infiltration on such buildings.
What problem does this paper attempt to address?