Energy saving potential for space heating in Chinese airport terminals: The impact of air infiltration

Xiaochen Liu,Tao Zhang,Xiaohua Liu,Lingshan Li,Lin Lin,Yi Jiang
DOI: https://doi.org/10.1016/j.energy.2020.119175
IF: 9
2021-01-01
Energy
Abstract:<p>Airport terminals are key infrastructures with rapid development, which have a high level of energy consumption, especially for space heating in cold climate zones. In this study, large-scale field investigations from 2012 to 2019 into the space heating performance were conducted in eighteen Chinese airports terminals. It is indicated that severe air infiltration (air change rate: 0.06–0.56 h<sup>-1</sup>) is almost the most significant factor influencing space heating (18%–71% of total heat loss). A simplified model of airport terminals is then established and validated to evaluate the energy saving potential of reducing air infiltration. The air tightness of the airport terminals can be quantified by the field investigated parameters, i.e., the discharge coefficients of the roof (<em>c</em><sub><em>r</em></sub>: 1×10<sup>-5</sup>–1×10<sup>-3</sup>) and the gates (<em>c</em>: 0.25–0.55). Improving the air tightness and using the radiant floor in airport terminals can achieve an average reduction of annual heating demand by 84%. Thus, reducing air infiltration provides a feasible approach towards the goal of "zero energy for space heating" in airport terminals. This study sheds light on the current situation of high energy consumption for space heating in airport terminals and provides guidelines for both design and operation.</p>
energy & fuels,thermodynamics
What problem does this paper attempt to address?
The problem that this paper attempts to solve is the high energy consumption problem in the heating process of Chinese airport terminals in winter, especially the high heat loss caused by air infiltration. The study points out that severe air infiltration is almost one of the factors that most affect the heating efficiency, accounting for 18% - 71% of the total heat loss. Through large - scale on - site investigations and the establishment of a simplified model, the study aims to reveal the current situation of air infiltration in Chinese airport terminals in winter and quantify the energy - saving potential brought by reducing air infiltration. Specifically, the research objectives include: 1. **Reveal the current situation**: Through large - scale on - site investigations carried out in 18 airport terminals in China from 2012 to 2019, reveal the current situation of air infiltration in Chinese airport terminals in winter. 2. **Quantify the energy - saving potential**: Based on the on - site investigation results, establish a simplified model to calculate the air permeability and heating load, and evaluate the energy - saving potential of reducing air infiltration. 3. **Propose solutions**: By analyzing the impact of air infiltration on the indoor thermal environment, propose feasible methods to reduce air infiltration, thereby achieving the energy - saving goal. The study found that improving the airtightness of the terminal building and using radiant floor heating can reduce the annual heating demand by an average of 84%, which provides a feasible way to achieve "zero - energy - consumption heating". These findings not only help to understand the reasons for the high energy consumption of current Chinese airport terminals, but also provide guiding suggestions for design and operation.