Comprehensive Protection Method for DC Collection Cable of Large-Scale Photovoltaic Plant Based on Fault Current Limiter

Moduo Yu,Wentao Huang,Nengling Tai,Haroon Nadeem,Xinze Xi
DOI: https://doi.org/10.1109/pesgm40551.2019.8973397
2019-01-01
Abstract:This paper proposes a comprehensive protection method based on current-limiting reactor for DC collection system of large-scale PV plant. In the method, the fault current limiter is connected to DC cable in cascade, for suppressing fault currents and extending protection action time. Then propose a current-limiting reactor parameter calculation method based on breaking capacity of circuit breaker and time limit constraints of protection action. Finally, improve means for obtaining differential current, and achieve a cable protection by locating the cable fault using voltage and current data on both ends of the cable. Even affected by the fault type, location and transition resistance, the method still locates the fault accurately with sample and reliable fault criterion. Meanwhile, the correct protection action can still be achieved without data synchronization. This method can be applied to DC transmission and distribution networks at the same time. It has high application value for protection and fault location of DC cables.
What problem does this paper attempt to address?