One Quick-Action Protection Scheme for VSC-HVDC Transmission Lines with Considering the Frequency-Dependent Characteristics of Cables
Peiyao Liu,Guobing Song,Xu Chu,Ting Wang
DOI: https://doi.org/10.1109/appeec.2016.7779933
2016-01-01
Abstract:The protection strategy for VSC-HVDC transmission has a poor performance in practice, and it is necessary to explore new protection schemes. Most transmission lines of VSC-HVDC use the cables which have obvious frequency-dependent characteristics, and large capacitors are installed at both ends of transmission lines, making it possible to construct the new single-end protections. This paper analyzes the circuits' topology of VSC-HVDC transmission line under internal and external faults, and then defines the transfer impedance of fault component circuits. With considering the frequency-dependent parameters of cables, it is found that the impedance of high frequency under external faults is quite larger than that under internal faults, which means that the high-frequency current can be used to distinguish internal and external faults. The simulation results prove the validity and good performance of the proposed protection scheme.
What problem does this paper attempt to address?