An Adaptive Wide Area Fault Location Algorithm for Transmission Lines With Optimal PMU Placement

LUO Shenzeng,LI Yinhong,CHEN Bo,SHI Dongyuan,LI Benyu,ZHAI Haiyan,ZHAO Ming
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.151998
2016-01-01
Abstract:An adaptive wide area fault location algorithm for transmission lines with optimal phasor measurement unit (PMU) placement was proposed to solve the transmission line fault location problem under the conditions of lacking complete information. On the basis of analyzing fault-location observability based fault location principle, optimal PMU placement model for transmission network fault-location observability considering zero injection bus was established. Then the wide area fault location algorithm based on fault-location zone which was divided according to the grid topology and PMU installed nodes was proposed. When the grid topology changes, the fault-location zone was also updated correspondingly with partial modification. After the line failure, the fault-location zone that the fault line belongs to was quickly determined using PMU measurement. Without fault line information requirement, the adaptability of the proposed fault location method was improved. Simulation results based on PSCAD/EMTDC and Matlab have shown that the proposed method requires fewer PMU devices to achieve transmission network fault-location observability. The fault location algorithm based on fault-location zone has strong adaptability and high accuracy and is suitable to grid topology changes as well as various fault types, fault positions and fault resistances.
What problem does this paper attempt to address?