Study of Distance Protection Scheme for Transmission Line Including UPFC

KONG Xiangping,YUAN Yubo,GAO Lei,LI Peng,LIN Jinjiao
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.152356
2016-01-01
Abstract:Based on the practical unified power flow controller (UPFC) project, the influence of UPFC on the distance protection was analyzed. Moreover, a novel distance protection scheme which consists of novel distance protection zone 1, as well as conventional distance protection zone 2 and zone 3 was proposed. The proposed novel distance protection zone 1 was based on the differential equation model of the transmission line. With the local voltage and current signals, it could obtain the distance from the fault point to the relay location, and effectively distinguish between the internal fault and external fault. The proposed distance protection zone 1 could completely replace the conventional distance protection zone 1, and realize effective cooperation with the conventional distance protection zone 2 and zone 3. Consequently, the correct action of the novel distance protection scheme could be guaranteed. The simulation study verifies that the excellent performance of the proposed distance protection scheme would not be affected by the operational mode and control parameters of UPFC, and can satisfy the safe operation requirements of the power systems.