Impact Evaluation for Distance Protection of Southern Suzhou 500kV UPFC

Liang Zhang,Bin Zhou,Peng Li,Yubo Yuan,Jingnan Xu,Xiangping Kong
DOI: https://doi.org/10.1109/ICIEA.2019.8834339
2019-01-01
Abstract:The 500kV unified power flow controller (UPFC) has been built in Southern Suzhou, which improves the power supply capacity of the grid. However, due to the UPFC access, the impedance value of the conventional distance protection measurement could not truly reflect the fault location. To solve it, the impact of the UPFC access on the transmission line protection is studied in this paper. Firstly, the model of unified power flow controller based on modular multilevel converter (MMC-UPFC) was established. The control strategies for both the series and parallel side converters were designed. Then, by the fault sequence network diagram, the equivalent circuit model is given, and the influence of the UPFC access transmission line on the traditional distance protection is analyzed in details. Finally, simulations were carried out in PSCAD/EMTDC to verify the different mode effect on the traditional distance protection, when a single-phase ground fault by the metal occurs. The results show that in STATCOM mode, the apparent impedance is affected by the reactive power injected or absorbed, and it is more severe in UPFC mode.