Configuration Scheme of Transmission Line Protection for Flexible HVDC Grid

DONG Xinzhou,TANG Lanxi,SHI Shenxing,QIU Yufeng,KONG Ming,PANG Hui
DOI: https://doi.org/10.13335/j.1000-3673.pst.2017.3063
2018-01-01
Abstract:Because of capacity limitation of DC circuit breaker, transmission line protection of flexible HVDC grid must have fast operation speed. Configuration scheme of the transmission line protection for flexible HVDC grid is proposed. Main protection for the transmission line adopts single-end quantities based protection principle to meet need for fast speed of protection. Decoupling method and fault pole selection, accompanied with identification of noise, lightning and other disturbances, are essential to ensure reliability of the protection. Backup protection for the transmission line adopts pilot protection with high sensitivity, including travelling wave differential protection and reactive power based directional protection, and coordinates with main protection in time sequence. During fault on DC side, backup protection should be faster than protection at AC side. Difference and similarity among the transmission line protections for flexible HVDC grid, traditional HVDC system and AC system are analyzed and summarized, providing important reference for HVDC grids in construction in China.