Abstract:The DC‐link fault is a key issue for the flexible high‐voltage direct current system using modular multilevel converter ( MMC‐HVDC) . An auxiliary equipment based processing strategy for MMC‐HVDC DC faults is proposed , namely , a novel scheme by bidirectional thyristors in collaboration with a breaker‐type zero‐loss fault current limiter . The DC‐protections based on natural decay of the fault DC current and their shortcomings are analyzed first . It is then proposed that the bidirectional thyristors rather than back‐to‐back ones are configured and controlled on the AC‐side to simplify the control loop . The bidirectional thyristors are controlled to cooperate with the appropriately designed breaker‐type zero‐loss fault current limiter , which can possess fast current limiting ability while reducing the long short‐circuit current rush to AC system during the clearance of the DC‐link fault . And the corresponding DC‐fault detection and recovery strategy is presented . PSCAD based simulation results finally verify the validity of the proposed protection scheme .