Error Sources of Grounding Grid Resistance Measurement Using Overhead Ground Line

Wei LIU,Wei NIE,Zhi CHEN,Peng XU
DOI: https://doi.org/10.13296/j.1001-1609.hva.2012.08.009
2012-01-01
Abstract:The authors analyze error sources of grounding grid resistance measurement making use of overhead ground line as current or voltage wire,and find the principal source is due to the overhead ground line uninsulated with earth.Therefore,a mathematical mode is established to investigate the effects of substation grounding resistance,current loop resistance,tower grounding resistance,and type of overhead ground line on the measurement error of grounding grid resistance.It is concluded that the ground voltage measurement error of the grounding grid is mainly affected by short range of the overhead ground line.In order to reduce the measurement error of grounding grid resistance by large-current method,overhead ground line ought to be insulated with earth within test scope or a manual wire-release way be taken.