A Test Study on Fault Diagnosis of the Grounding Grid Based on Surface Potential

Lei Su,Fenghua Wang,Shaojing Wang,Yadong Liu
DOI: https://doi.org/10.3969/j.issn.1000-3886.2016.03.015
2016-01-01
Abstract:To improve the accuracy of fault diagnosis of the transformer substation grounding grid,this paper studies regular and irregular shapes of grounding grid models,and makes a test analysis on the surface potential distribution in the case of simulated typical fault of the grounding grid.The test results show that,by analyzing the surface potential distribution of the grounding grid,we can quite accurately determine the location and type of faults in the grounding grid conductor of the transformer substation.In the case of grounding grid faults of pseudo soldering,sealing off or corrosion,the fault location and the surface potential of adjacent conductor sections may rise or drop accordingly.The research results constitute an important supplement to the method of fault diagnosis of the grounding grid based on surface potential distribution.