Continuous Operation of Smart Transformer-fed Distribution Grid with Single-phase Faults

Rongwu Zhu,Marco Liserre
DOI: https://doi.org/10.1109/ecce.2018.8558226
2018-01-01
Abstract:Solid-state transformer-based Smart Transformer (ST) allows integrating energy storages and electric vehicle charging stations, while offering ancillary services to electric grid. The continuity of service in power supply as a basic requirement for the electric grid operation is threatened and interrupted by grid faults in the conventional distribution transformer (CDT)-fed electric grid, but can be ensured by the ST. Unlike the CDT, the ST can switch from three-phase operation mode to two-phase operation mode, ensuring continuous power supply in two healthy phases and reducing outage area, during single-phase to ground faults (SFGFs). An improved voltage control strategy is proposed to balance the power losses reduction in neutral conductor and voltage oscillation suppression in DC-link during two-phase operation mode. This paper focuses on the performances design of ST voltage control during the two-phase operation mode to improve the grid voltage transient performances. The simulation and experimental results clearly verify the effectiveness and correctness of the proposed strategy.
What problem does this paper attempt to address?