Temperature-Rise Performance of 126 Kv Single-Break Vacuum Circuit Breakers with 4 Types of AMF Contacts

Shaowei Liu,Zihan Wang,Haomin Li,Yuanzhao Li,Yingsan Geng,Zhiyuan Liu,Jianhua Wang
DOI: https://doi.org/10.1109/deiv.2018.8537170
2018-01-01
Abstract:The objective of this paper is to compare the temperature-rise performance of 4 kinds of AMF contacts designs of 126 kV vacuum circuit breakers (VCBs). The 4 AMF contacts designs are 2/3 coil-type AMF contact, 3/4 coil-type AMF contact, horseshoe-type AMF contact and slotted horseshoe-type AMF contact, respectively. The finite element method simulation results showed that hot state AC bulk resistance of the 4 designs of AMF contacts are 30.23, 36.93, 23.98 and 16.25 μΩ, respectively under 3150 A. Temperature distribution of the 4 VCBs were calculated by employing finite volume method. Temperature-rise simulation models were verified by experimental results under 2500 A. The errors between simulation results and experimental results for 5 measuring points around the VI were less than 10% and the maximum error was 36.75%, which located at the terminals of the 126 kV VCB. The thermal simulation results suggest the VCB with slotted horseshoe-type AMF contact has the best temperature-rise performance among the 4 types of 126 kV VCBs design, and it is the only one design that meets the GB standard requirement under a nominal rated current of 3150 A. The maximum of temperature-rise of the 126 kV VCB with slotted horseshoe-type contact was 66.04 K.