Research on the Detecting Effectiveness of On-site Lightning Impulse Test for GIS Equipment with Insulation Defects

Tao Wen,Qiaogen Zhang,Jingtan Ma,Xuandong Liu,Zhicheng Wu,Lingli Zhang,Junping Zhao,Naoyuki Shimomura,Weijiang Chen
DOI: https://doi.org/10.1109/tdei.2018.006961
IF: 2.509
2018-01-01
IEEE Transactions on Dielectrics and Electrical Insulation
Abstract:On-site lightning impulse (LI) test waveform, restricted by the large load capacitance and impulse generator's inherent inductance, has a long wavefront time T-f compared with standard LI, called non-standard LI. The non-standard LI test has been carried out in the field. But its insulation defect detecting effectiveness is not clear. In this paper, a generating system of impulses with different waveform parameters, including double exponential impulses with different wavefront times in the range of 0.08 similar to 23.5 mu s and an oscillating LI with wavefront time around 10 mu s, was established. The insulation characteristics of SF6 gas gap with highly inhomogeneous electric field under impulses with different waveform parameters were investigated. Experimental results show that the insulation defects detecting effectiveness of oscillating LI with long T-f around 10 mu s is lower than that of standard LI. T-f plays an important role in the insulation defects detection. With T-f increases, the 50% breakdown voltages for rod-plane gaps have an increased trend. The V-t curve presents a U-shape. Prospective voltage is introduced to evaluate the insulation defects detecting effectiveness. The prospective voltage-time characteristics confirm the conclusion that with the increase of impulse voltage T-f, the detection effectiveness for GIS insulation is reduced. The gap distance has influence on the shape of V-t curve. With distance increase, the 50% breakdown voltage of the gap is more sensitive to the wavefront time T-f and voltage rise rate dU/dt. Corona stabilization effect is not just in relationship with the rise rate of impulse, but also with electrode structure and gas pressure. The critical dU/dt for corona stabilization is calculated for different rod-plane gaps.
What problem does this paper attempt to address?