Abstract:The chromatographic column separation equations are used to improve the reliability of DGA(Dissolved Gases Analysis) for the DGA-based on-line monitoring of power transformers.The formulas for calculating the time of gases with different speeds retaining in chromatographic column are set when the temperature of column and the air pressure difference between input and output ports are constant.The relationship among peak width,plate number and remaining time is set according to plate theory,the relationship between peak width and gas velocity is set according to Van Deemter’s plate height equation,and the relationship among peak height,peak width and remaining time is set according to Gauss distribution principle.The distribution curve of output gases is thus obtained and the mathematical chromatographic column separation equation is created.Experiment is designed to determine the parameters of separation equation of GDX 502 + PORAPACK N chromatographic column,and result shows the calculating error less than 4 %.