Molecular Dynamic Simulation and Experimental Study on Gases Diffusion Characteristics and Coefficients in Transformer Oil

Huantong Shi,Wei Sun,Ran Zhuo,Zhiming Huang,Qiulin Chen,Lianhong Zhong,Yuan La,Xingwen Li,Mingli Fu
DOI: https://doi.org/10.1109/tdei.2024.3349993
IF: 2.509
2024-01-01
IEEE Transactions on Dielectrics and Electrical Insulation
Abstract:In power transformers, the degradation of insulating oil due to aging, overheating, and electric discharge leads to the production of characteristic gases including H 2 , CH 4 , C 2 H 2 , C 2 H 4 , C 2 H 6 , CO and CO 2 . The composition and concentration of these gases provide valuable insights into the operational condition of the transformer. Dissolved gas analysis (DGA) is a vital diagnostic and predictive technique for transformer faults, which is closely associated with the transportation of gases within the oil through convection and diffusion. This study employs a combination of molecular dynamics simulation and experimental measurement to determine the diffusion coefficients D of the seven characteristic gases in a naphthenic mineral oil across a range of temperature (T = 20~90 °C) and DC electric field strength ( E = 0~3 kV/mm). The calculated and measured results of the diffusion coefficients exhibit a strong agreement, demonstrating a positive correlation with temperature following D∝e -a/T , in which the influence from a weak DC electric field ranging from 0 to 3 kV/mm could be negligible.
What problem does this paper attempt to address?