Boundary conditions for perforated inlet panels in simulations of airflow inside clean rooms

赵彬,曹莉,李先庭
DOI: https://doi.org/10.3321/j.issn:1000-0054.2003.05.031
2003-01-01
Abstract:The airflow pattern inside a 'laminar flow' clean room with ventilation through perforated panels was analyzed numerically, using a specially developed inlet boundary condition for the flow through the perforated inlet panels. The clean room is 2.1 m high and 4 m wide with exhaust ducts that are 0.4 m high. The air supply Reynolds number is 5 × 10 4. A N-point air supply model was used to accurately simulate the inflow mass and momentum rates at the air supply openings, without changing the location and figuration of the diffusers. The boundary condition was used in the 3-D computational fluid dynamics software STACH-3 to model the airflow inside the clean room with full ceiling air supply and the air return at the bottom of the two side walls. The calculating results agree well with the experimental data.
What problem does this paper attempt to address?