Numerical Analysis about the Flow Pattern Resulted by Exhaust Air and Supply Air

Penglei Zhang,Chao Liang,Xianting Li
DOI: https://doi.org/10.26868/25222708.2013.2112
2013-01-01
Abstract:Traditionally, jet flow is believed to be strong enough to supply air farther than exhaust air; exhaust air is believed to be only dominant near the outlet. However, there is little investigation about the difference between supply air and exhaust air in ventilated room. One two-dimensional ventilated room is taken as an example, in which both supply air mode and exhaust air mode are simulated by using CFD software. The flow pattern in the room without infiltrations and with infiltrations are compared. The numerical results indicate that the flow pattern resulted by exhaust air is almost the same with that resulted by supply air when there is no infiltration. When the infiltration exists, the flow pattern for exhaust air is different from that for supply air. When infiltration exists almost everywhere, the influence of exhaust air exists only near the outlet, while the influence of supply air has no obvious difference with the case without infiltration. Moreover, the specific influence caused by infiltration dimension is discussed. The study can explain the difference between exhaust air and supply air, and may be helpful for the design of different flow pattern.
What problem does this paper attempt to address?